@ -18,6 +18,6 @@ This is always caused by one of the following:
|
||||
3. Trusted range is too short. Trusted ranges should either be zero to disable the functionality, or set large enough that all your devices can talk to each other.
|
||||
4. Facility authentication keys don't match. Facility authentication keys need to be set on all or none of the devices in the network. If set, they need to all match. Please double check them.
|
||||
|
||||
There are specific other cases as well:
|
||||
There are specific cases as well:
|
||||
1. PLC's with the same reactor unit ID will not connect if another PLC with that ID is already connected. Make sure you only have one PLC configured per reactor.
|
||||
2. Devices with different communications protocol versions (can occur if not all devices are up-to-date) will not be able to talk to each other. Make sure devices are up-to-date.
|
||||